Shelly Pro 3EM-120A V2 DIN-Rail Energy Meter for EcoFlow STREAM 5000

  • Measure grid import and export to support energy management with a compatible EcoFlow STREAM 5000 or STREAM AC 5000 system.
  • Monitor single-phase or three-phase installations using three included 120A current-transformer clamps.
  • View live electrical readings and stored energy data through Ethernet or Wi-Fi, with no separate Shelly hub required.

Shelly Pro 3EM-120A V2 energy meter for EcoFlow STREAM 5000

The Shelly Pro 3EM-120A V2 is a DIN-rail energy meter for monitoring electricity consumption and generation in homes and suitable commercial premises. Shelly identifies the V2 as model SPEM-003CEBEU, an identifier listed by EcoFlow for STREAM 5000 and STREAM AC 5000. When correctly installed and paired, it supplies the grid-exchange measurements used by the EcoFlow system’s energy-management functions.

Key features

  • EcoFlow-compatible model identification: SPEM-003CEBEU appears in EcoFlow’s STREAM 5000 compatibility list. Confirm the supplied unit and supported firmware before commissioning.
  • Flexible measurement: monitor a single-phase supply, a three-phase supply or three selected circuits on the same phase, using the appropriate wiring and configuration.
  • Detailed electrical readings: measure voltage, current, active and apparent power, power factor and accumulated energy, with Class B active-energy accuracy stated by Shelly.
  • Local data and networking: Ethernet, 2.4GHz Wi-Fi, an embedded web interface and at least 45 days of one-minute records according to the detailed manufacturer specification.
  • Automation options: scripting, webhooks and MQTT support, plus Matter support after the required firmware update.

Where to use

Use the Shelly Pro 3EM-120A V2 for whole-home monitoring, compatible EcoFlow STREAM installations, offices, retail premises, agricultural buildings and selected commercial distribution-board applications. It measures the circuits where its CT clamps are installed; it does not automatically identify every individual appliance.

For EcoFlow integration, the installer must position the sensors and configure the meter to measure the correct grid connection point. A typical single-phase UK home does not need a three-phase supply to use this meter.

This device measures energy and has no built-in load-switching relay. Controlling a larger load requires the optional Shelly Pro 3EM Switch Add-on and a suitably rated external contactor, specified separately. It is not a circuit breaker or a replacement for electrical protective devices.

Installation and EcoFlow compatibility

A qualified electrician must install the meter, CT clamps, voltage-reference wiring and suitable protective devices in an appropriate enclosure. Energian can help with product selection and installation through trusted partners.

Confirm model SPEM-003CEBEU on the supplied V2 device and check the current EcoFlow app and firmware requirements. EcoFlow also lists SPEM-003CEBEU120; compatibility must not be assumed for the 400A or 3CT63 variants.

Do not assume that this meter duplicates every function of EcoFlow’s Smart Meter Dual CT. In particular, EcoFlow’s Dual CT circuit-protection features must not be attributed to the Shelly meter without confirmation.

Technical specifications

Specifications below use Shelly’s current Pro 3EM 120A V2 product documentation. The attached user guide is dated 48/2022 and differs in some radio and storage specifications; use the current instructions applicable to the delivered device.

Specification Value
Product identification and package contents
Brand Shelly
Product designation Shelly Pro 3EM 120A V2
Device model stated on the V2 product page SPEM-003CEBEU
Default device SSID ShellyPro3EM-XXXXXX
Meter type DIN-rail AC energy meter with external current transformers
Supported electrical arrangements Single-phase or three-phase; three separate circuits of one phase can also be monitored
Standard package 1 × energy meter; 3 × 120A current transformers; installation guide
Optional neutral CT Additional compatible CT required; not included
EcoFlow-compatible model identifiers SPEM-003CEBEU and SPEM-003CEBEU120 are listed by EcoFlow for STREAM 5000 / STREAM AC 5000
EcoFlow connection qualification Requires supported app/firmware, correct network setup and pairing. Confirm the exact supplied device identifier.
Built-in switching relay No
Optional load control Shelly Pro 3EM Switch Add-on with an appropriately rated external contactor; not included
Electrical supply and protection
AC supply voltage 100–260V AC
Supply frequency 50/60Hz
DC supply Not supported
Power consumption <3W
Manufacturer-specified external protection B- or C-curve; maximum rated current 16A; minimum breaking capacity 6kA; energy-limiting class 3
Protection-rating clarification The 16A maximum relates to protection of the meter’s wired supply/voltage-reference connections. The 120A rating relates to CT measurement, not current carried through its voltage terminals.
Measurement capabilities and accuracy
Measurement method External CTs with wired voltage-reference connections
Voltage measurement range per phase, RMS 100–260V
Voltage accuracy ±1%
Current measurement range 0–120A per phase; optional neutral measurement with an additional CT
Compatible CT designation CT 120A
Current accuracy, 2–120A ±1%
Current accuracy, 1–2A ±2%
Current accuracy, below 1A ±5%
Active-energy accuracy Class B; IEC 62053-21 compliance stated by Shelly based on manufacturer testing
Measured quantities Active and apparent power; active and apparent energy; power factor; fundamental active and fundamental reactive energy; voltage and current
Energy-flow measurement Four-quadrant measurement; consumption and generation monitoring
Phase-sequence error detection Configurable option
Channel-to-channel calibration Supported; minimum 500W load per channel
No-load threshold 30VA per channel
Low-load energy-recording qualification Shelly states that when the total load falls below its specified threshold, measured power remains visible but consumed energy is not accumulated in the energy statistics.
Internal temperature sensor Yes, with reporting
Optical energy indication Energy-count LED with pulse frequency dependent on measured energy flow
Data storage and local access
Detailed specification: on-device records At least 45 days at one-minute resolution
Storage qualification Shelly also advertises 60 days elsewhere on the V2 product page. The detailed specification’s minimum 45-day figure is used here.
Memory type Non-volatile storage
Timekeeping Real-time clock retains timestamps if connection to the SNTP server is lost
Data export CSV for recorded electrical values; JSON through RPC
Local management Embedded web interface
Standalone operation Supported on a local LAN and/or Wi-Fi network
Shelly cloud requirement Optional for standalone Shelly monitoring; EcoFlow features have their own connection requirements
Dedicated Shelly hub Not required for LAN/Wi-Fi operation
Networking and automation
Ethernet RJ45 port
Wi-Fi protocol 802.11 b/g/n
Wi-Fi band 2.4GHz
RF band in current specification 2,400–2,495MHz
Maximum RF power in current specification <20dBm
Published Wi-Fi range Up to 30m indoors and 50m outdoors, depending on local conditions
Bluetooth protocol in current specification 4.2
Published Bluetooth range Up to 10m indoors and 30m outdoors, depending on local conditions
Bluetooth role Device inclusion/setup
Matter Matter-upgradable after updating to the required firmware; this does not itself establish EcoFlow compatibility
Network protocols MQTT, HTTP and WebSocket
Inbound connection security TLS support
MODBUS Supported for voltage, current, power and energy data
Webhooks 20, with up to 5 URLs per webhook
Scripting Supported
CoAP Not supported
Physical specifications and terminals
Dimensions, H × W × D 94 × 19 × 69mm, ±0.5mm
Device weight 62g ±1g; excludes CTs and packaging
Mounting DIN rail
Housing White plastic
Maximum screw-terminal torque 0.4Nm
Conductor cross-section 0.5–2.5mm²; solid, stranded or bootlace-ferrule termination
Conductor stripping length 6–7mm
Voltage inputs A, B and C phase inputs; N neutral. C also supplies device power.
Current-transformer inputs IA, IB and IC for phase measurements; IN for optional neutral measurement
Add-on interface Shelly proprietary serial interface; hazardous voltage may be present when powered
User button Short press operates an attached switch add-on; hold 5 seconds for device access point; hold 10 seconds for factory reset
Indicators Power, Wi-Fi, LAN and energy count
Processor ESP32-D0WDQ6
Flash memory 16MB
Environmental and installation requirements
Ambient operating temperature −20°C to +40°C
Relative humidity 30–70%
Maximum altitude 2,000m
Installation environment Suitable electrical enclosure; do not install where the device can get wet
Installation personnel Qualified electrician
Isolation Isolate and prove dead before installing or changing electrical connections.
LAN connection precaution Connect or disconnect the Ethernet cable only while the meter is powered off, as instructed by Shelly.
Optional neutral CT Not required for standard phase-current measurement; specify separately if neutral monitoring is needed.
Compliance documentation EU declaration of conformity, UKCA declaration of conformity and UK PSTI statement of compliance available from Shelly’s current product documentation