SolisStorage EverCore 261kWh Battery and 125kW Hybrid Inverter System

  
By Solis

Bulk Supply Quote

Delivery available

SolisStorage EverCore 261kWh Battery and 125kW Hybrid Inverter System

  • One outdoor cabinet holds 258.3kWh of usable LFP storage, a 125kW three-phase hybrid inverter and up to 250kW of solar input.
  • Keeps critical loads running in a grid outage, with backup switchover in under 10ms.
  • Built-in 5kW air conditioning plus layered fire protection: aerosol, explosion relief valve and fire water inlet.

SolisStorage EverCore 261kWh battery and 125kW hybrid inverter system

The SolisStorage EverCore 261kWh battery and 125kW hybrid inverter system (EverCore-261kWh-125kW-NV) pairs a 261.2kWh LFP battery cabinet with a Solis S6-EH3P125K10-NV-YD-H inverter. It stores solar or off-peak grid energy, cuts peak demand and backs up three-phase loads. Battery management, monitoring and connections for grid, load and a diesel generator are built in.

Key features

  • Thirteen 20.1kWh battery packs built from 3.2V / 314Ah LFP cells, rated for 8,000 cell cycles (cell manufacturer data, 25°C, 0.5P, 70% SOH).
  • Rated at 125kW / 125kVA on-grid. Backup output can briefly reach 1.6× rated power for 200ms to help start loads.
  • Ten MPPTs and 20 PV strings, 1,000V maximum input and a 150–950V MPPT range.
  • Off-grid parallel operation of up to 10 units, with a SMARTLOAD/GEN port and dry contact for diesel generator control.
  • SolisCloud app setup over Bluetooth, plus WiFi, LAN, CAN, RS485, DRM, 5 digital inputs and 4 outputs (4G optional).

Where to use

This system suits larger three-phase commercial and industrial sites. Examples include logistics and distribution centres, cold stores, factories, farms, hospitals, campuses and EV charging hubs.

Typical uses are solar self-consumption, peak shaving, time-of-use tariff shifting, backup for critical loads, and off-grid or weak-grid sites running alongside a generator.

Installation and site requirements

The system is not plug-and-play. The cabinet and inverter ship separately and are assembled on site. Lifting needs a crane or forklift rated for at least 3.5 tonnes. Energian can arrange design, installation and commissioning through trusted partners.

Install outdoors on a level, non-combustible base able to carry 5 tonnes per unit. Keep at least 500mm behind the cabinet and about 2,500mm clear in front. Only qualified electricians should install it, and grid connection needs DNO approval.

Solar panels, mounting, cabling, switchgear and grounding are not included. They can be quoted to suit your site.

SolisStorage EverCore 261kWh / 125kW technical specifications

Specification EverCore-261kWh-125kW-NV
System
Rated energy capacity 261.2kWh (manual: 261.248kWh)
Usable energy capacity 258.3kWh (30–35°C, 0.3C, 100% DOD, within one month of manufacture)
Nominal charging / discharging power 125kW / 125kW
Max. cycle rate 0.5P
Max. cycle efficiency 89% (cell test at 25 ±2°C, 0.5P, AC output 380 or 400Vac)
Dimensions (W × H × D) 1,850 × 2,230 × 1,600mm
Dimensions without inverter (W × H × D) 1,400 × 2,230 × 1,600mm
Weight 2,900kg (cabinet) + 170kg (inverter) (manual: cabinet 2,950kg)
Operating temperature range -25 to +55°C (manual: charging 0 to +55°C, discharging -25 to +55°C)
Storage temperature range 0 to +40°C (manual: -20 to +45°C)
Transportation temperature -30 to +55°C
Operating humidity range ≤95% (non-condensing)
Max. operation altitude 4,000m (derating above 2,000m)
System temperature control mode Industrial-grade air-conditioning (cabinet); air cooling (pack); intelligent fan-cooling (inverter)
Fire suppression mode Default: aerosol, explosion relief valve, fire water inlet, audible and visual alarm. Optional: flammable gas detector, explosion relief panel, explosion-proof exhaust fan
Fire detection Smoke detector and temperature detector (standard); flammable gas detector (optional); DN65 fire water inlet on the rear of the cabinet
Ingress protection IP55 (cabinet) + IP66 (inverter)
Anti-corrosion class (battery cabinet) C4 / C5 (optional)
Anti-corrosion class (inverter) C5
Noise (rated operating condition) 75dB(A) at 1m
Lightning protection Type II (AC port), Type II (PV & battery)
Protection mode Anti-islanding protection, residual current detection, insulation resistance detection, AC overcurrent protection, AC cable connection protection
Auxiliary power supply 220Vac, approx. 4kW
Communication protocol (cabinet) TCP/IP, CAN, RS485
Certification standards (datasheet) IEC 62619, IEC 61000-6-2/4, IEC 62040, IEC 63056, IEC 62477, UN38.3
Compliance standards (manual) UN38.3, IEC 62619, IEC 63056, IEC 62477-1, IEC 61000-6-2 / IEC 61000-6-4, UN3480
Battery
Cell type LFP 3.2V / 314Ah (EVE MB31, 5.6 ±0.2kg)
Cell cycle life 8,000 (cell manufacturer data at 25 ±2°C, 0.5P charge and discharge, SOH = 70%)
System battery configuration 1P260S
Rated voltage 832V
Operating voltage range 754–936V
Rated DC current 157A
Number of battery packs 13
Battery pack model PACK-1P20S-314-01
Battery pack capacity 20.1kWh
Battery pack rated voltage / range 64V / 58–72V
Battery pack charge and discharge rate ≤0.5C
Battery pack weight 138kg
Battery pack dimensions (W × H × D) 435 × 230 × 904mm
Battery pack ingress protection IP20
Battery pack storage / transport temperature 0 to +40°C / -10 to +45°C
Balancing mode Passive cell balancing
Pack communications port CAN 2.0
Inverter
Inverter model S6-EH3P125K10-NV-YD-H
Rated output power 125kW
Max. apparent output power (on-grid) 125kVA
Rated grid voltage 3/N/PE, 220V / 380V; 3/N/PE, 230V / 400V
Rated grid frequency 50Hz / 60Hz
AC grid frequency range 45–55Hz / 55–65Hz
Rated output current 189.9A / 180.4A
Max. apparent output power (off-grid) 1.6 × rated power, 200ms (manual: backup port 1.4 × for 10s or 1.6 × for 200ms)
Back-up switch time <10ms
Power factor >0.99 (0.8 leading – 0.8 lagging)
THDi / THDv (at linear load) <2% / <3%
Max. usable PV input power 250kW
Recommended max. PV array size 250kW
Max. input voltage 1,000V
Rated voltage 600V
Start-up voltage 180V
MPPT voltage range 150–950V
Max. input current 10 × 42A
Max. short circuit current 10 × 60A
MPPT number / max. input strings number 10 / 20
Communication Standard: WiFi + LAN + Bluetooth, CAN-BMS × 2, CAN-Parallel × 2, RS485-Meter, RS485, DRM, DI × 5, DO × 4. Optional: 4G
Max. parallel quantity (off-grid) 10
AC ports Grid, Backup, SMARTLOAD/GEN (diesel generator); generator auto-start via DO dry contact
Thermal management (air conditioner)
Refrigerant / filling amount R134a / 1.6kg
Rated cooling / heating capacity 5kW / 3kW
Rated power (cooling / heating) 2.4 / 3.3kW at 50Hz; 2.9 / 3.4kW at 60Hz
Power supply 1/PE AC 230V (50Hz / 60Hz)
Maximum operating current 17.6A
Ambient temperature -40 to +50°C
Operating modes Cooling, heating, dehumidification, air supply
Net weight 105kg
Installation
Foundation Concrete, steel structure or other non-combustible surface; bearing capacity 5 × n tonnes (n = number of units); horizontal deviation ≤±10mm; flatness ≤±4mm per 2m
Site selection Outdoor, well ventilated, above the highest historical water level; ≥2,000m from airports, landfill, riverbanks, coasts or dams; ≥50m from residential areas
Clearances (multiple systems) Back to back ≥500mm; facing units ≥2,500mm; back to wall ≥500mm; front to wall 2,500mm recommended (follow local fire authority requirements)
Max. cable distances Inverter to battery 30m (optical fibre for 30–100m); inverter to inverter 60m; battery to battery 30m
Recommended cable sizes Grid 95–150mm²; Backup 70–95mm²; SMARTLOAD/GEN 70–95mm²; PE 50–75mm²; cabinet earth 25mm²
Lifting Crane >3.5t, 4 cables >1m, acceleration ≤0.2g; hooks for 24mm holes, WLL ≥1.8t each; forklift ≥3.5t