SolisStorage EverCore 261kWh Battery and 125kW Hybrid Inverter System
- One outdoor cabinet holds 258.3kWh of usable LFP storage, a 125kW three-phase hybrid inverter and up to 250kW of solar input.
- Keeps critical loads running in a grid outage, with backup switchover in under 10ms.
- Built-in 5kW air conditioning plus layered fire protection: aerosol, explosion relief valve and fire water inlet.
SolisStorage EverCore 261kWh battery and 125kW hybrid inverter system
The SolisStorage EverCore 261kWh battery and 125kW hybrid inverter system (EverCore-261kWh-125kW-NV) pairs a 261.2kWh LFP battery cabinet with a Solis S6-EH3P125K10-NV-YD-H inverter. It stores solar or off-peak grid energy, cuts peak demand and backs up three-phase loads. Battery management, monitoring and connections for grid, load and a diesel generator are built in.
Key features
- Thirteen 20.1kWh battery packs built from 3.2V / 314Ah LFP cells, rated for 8,000 cell cycles (cell manufacturer data, 25°C, 0.5P, 70% SOH).
- Rated at 125kW / 125kVA on-grid. Backup output can briefly reach 1.6× rated power for 200ms to help start loads.
- Ten MPPTs and 20 PV strings, 1,000V maximum input and a 150–950V MPPT range.
- Off-grid parallel operation of up to 10 units, with a SMARTLOAD/GEN port and dry contact for diesel generator control.
- SolisCloud app setup over Bluetooth, plus WiFi, LAN, CAN, RS485, DRM, 5 digital inputs and 4 outputs (4G optional).
Where to use
This system suits larger three-phase commercial and industrial sites. Examples include logistics and distribution centres, cold stores, factories, farms, hospitals, campuses and EV charging hubs.
Typical uses are solar self-consumption, peak shaving, time-of-use tariff shifting, backup for critical loads, and off-grid or weak-grid sites running alongside a generator.
Installation and site requirements
The system is not plug-and-play. The cabinet and inverter ship separately and are assembled on site. Lifting needs a crane or forklift rated for at least 3.5 tonnes. Energian can arrange design, installation and commissioning through trusted partners.
Install outdoors on a level, non-combustible base able to carry 5 tonnes per unit. Keep at least 500mm behind the cabinet and about 2,500mm clear in front. Only qualified electricians should install it, and grid connection needs DNO approval.
Solar panels, mounting, cabling, switchgear and grounding are not included. They can be quoted to suit your site.
SolisStorage EverCore 261kWh / 125kW technical specifications
| Specification | EverCore-261kWh-125kW-NV |
|---|---|
| System | |
| Rated energy capacity | 261.2kWh (manual: 261.248kWh) |
| Usable energy capacity | 258.3kWh (30–35°C, 0.3C, 100% DOD, within one month of manufacture) |
| Nominal charging / discharging power | 125kW / 125kW |
| Max. cycle rate | 0.5P |
| Max. cycle efficiency | 89% (cell test at 25 ±2°C, 0.5P, AC output 380 or 400Vac) |
| Dimensions (W × H × D) | 1,850 × 2,230 × 1,600mm |
| Dimensions without inverter (W × H × D) | 1,400 × 2,230 × 1,600mm |
| Weight | 2,900kg (cabinet) + 170kg (inverter) (manual: cabinet 2,950kg) |
| Operating temperature range | -25 to +55°C (manual: charging 0 to +55°C, discharging -25 to +55°C) |
| Storage temperature range | 0 to +40°C (manual: -20 to +45°C) |
| Transportation temperature | -30 to +55°C |
| Operating humidity range | ≤95% (non-condensing) |
| Max. operation altitude | 4,000m (derating above 2,000m) |
| System temperature control mode | Industrial-grade air-conditioning (cabinet); air cooling (pack); intelligent fan-cooling (inverter) |
| Fire suppression mode | Default: aerosol, explosion relief valve, fire water inlet, audible and visual alarm. Optional: flammable gas detector, explosion relief panel, explosion-proof exhaust fan |
| Fire detection | Smoke detector and temperature detector (standard); flammable gas detector (optional); DN65 fire water inlet on the rear of the cabinet |
| Ingress protection | IP55 (cabinet) + IP66 (inverter) |
| Anti-corrosion class (battery cabinet) | C4 / C5 (optional) |
| Anti-corrosion class (inverter) | C5 |
| Noise (rated operating condition) | 75dB(A) at 1m |
| Lightning protection | Type II (AC port), Type II (PV & battery) |
| Protection mode | Anti-islanding protection, residual current detection, insulation resistance detection, AC overcurrent protection, AC cable connection protection |
| Auxiliary power supply | 220Vac, approx. 4kW |
| Communication protocol (cabinet) | TCP/IP, CAN, RS485 |
| Certification standards (datasheet) | IEC 62619, IEC 61000-6-2/4, IEC 62040, IEC 63056, IEC 62477, UN38.3 |
| Compliance standards (manual) | UN38.3, IEC 62619, IEC 63056, IEC 62477-1, IEC 61000-6-2 / IEC 61000-6-4, UN3480 |
| Battery | |
| Cell type | LFP 3.2V / 314Ah (EVE MB31, 5.6 ±0.2kg) |
| Cell cycle life | 8,000 (cell manufacturer data at 25 ±2°C, 0.5P charge and discharge, SOH = 70%) |
| System battery configuration | 1P260S |
| Rated voltage | 832V |
| Operating voltage range | 754–936V |
| Rated DC current | 157A |
| Number of battery packs | 13 |
| Battery pack model | PACK-1P20S-314-01 |
| Battery pack capacity | 20.1kWh |
| Battery pack rated voltage / range | 64V / 58–72V |
| Battery pack charge and discharge rate | ≤0.5C |
| Battery pack weight | 138kg |
| Battery pack dimensions (W × H × D) | 435 × 230 × 904mm |
| Battery pack ingress protection | IP20 |
| Battery pack storage / transport temperature | 0 to +40°C / -10 to +45°C |
| Balancing mode | Passive cell balancing |
| Pack communications port | CAN 2.0 |
| Inverter | |
| Inverter model | S6-EH3P125K10-NV-YD-H |
| Rated output power | 125kW |
| Max. apparent output power (on-grid) | 125kVA |
| Rated grid voltage | 3/N/PE, 220V / 380V; 3/N/PE, 230V / 400V |
| Rated grid frequency | 50Hz / 60Hz |
| AC grid frequency range | 45–55Hz / 55–65Hz |
| Rated output current | 189.9A / 180.4A |
| Max. apparent output power (off-grid) | 1.6 × rated power, 200ms (manual: backup port 1.4 × for 10s or 1.6 × for 200ms) |
| Back-up switch time | <10ms |
| Power factor | >0.99 (0.8 leading – 0.8 lagging) |
| THDi / THDv (at linear load) | <2% / <3% |
| Max. usable PV input power | 250kW |
| Recommended max. PV array size | 250kW |
| Max. input voltage | 1,000V |
| Rated voltage | 600V |
| Start-up voltage | 180V |
| MPPT voltage range | 150–950V |
| Max. input current | 10 × 42A |
| Max. short circuit current | 10 × 60A |
| MPPT number / max. input strings number | 10 / 20 |
| Communication | Standard: WiFi + LAN + Bluetooth, CAN-BMS × 2, CAN-Parallel × 2, RS485-Meter, RS485, DRM, DI × 5, DO × 4. Optional: 4G |
| Max. parallel quantity (off-grid) | 10 |
| AC ports | Grid, Backup, SMARTLOAD/GEN (diesel generator); generator auto-start via DO dry contact |
| Thermal management (air conditioner) | |
| Refrigerant / filling amount | R134a / 1.6kg |
| Rated cooling / heating capacity | 5kW / 3kW |
| Rated power (cooling / heating) | 2.4 / 3.3kW at 50Hz; 2.9 / 3.4kW at 60Hz |
| Power supply | 1/PE AC 230V (50Hz / 60Hz) |
| Maximum operating current | 17.6A |
| Ambient temperature | -40 to +50°C |
| Operating modes | Cooling, heating, dehumidification, air supply |
| Net weight | 105kg |
| Installation | |
| Foundation | Concrete, steel structure or other non-combustible surface; bearing capacity 5 × n tonnes (n = number of units); horizontal deviation ≤±10mm; flatness ≤±4mm per 2m |
| Site selection | Outdoor, well ventilated, above the highest historical water level; ≥2,000m from airports, landfill, riverbanks, coasts or dams; ≥50m from residential areas |
| Clearances (multiple systems) | Back to back ≥500mm; facing units ≥2,500mm; back to wall ≥500mm; front to wall 2,500mm recommended (follow local fire authority requirements) |
| Max. cable distances | Inverter to battery 30m (optical fibre for 30–100m); inverter to inverter 60m; battery to battery 30m |
| Recommended cable sizes | Grid 95–150mm²; Backup 70–95mm²; SMARTLOAD/GEN 70–95mm²; PE 50–75mm²; cabinet earth 25mm² |
| Lifting | Crane >3.5t, 4 cables >1m, acceleration ≤0.2g; hooks for 24mm holes, WLL ≥1.8t each; forklift ≥3.5t |
Documents available for download
- SolisStorage EverCore datasheet
- SolisStorage EverCore user manual
- SolisStorage EverCore quick installation manual
Shipping
Shipping is available to the UK, Ireland, Africa, the Caribbean and worldwide. If a shipping rate is not shown at checkout, call +44 20 8064 0335 or email info@energian.co.uk for a quote. Delivery, unloading and site access are agreed for each order.
UK expert support
Our UK team can help you size an EverCore system, plan the PV array, generator and grid connection, and arrange installation. Contact us by phone, email or live chat, or visit our office for an in-person consultation.