SolisStorage EverCore 120kWh Battery and 60kW Hybrid Inverter System
- One outdoor cabinet holds 119.2kWh of usable LFP storage, a 60kW three-phase hybrid inverter and up to 100kW of solar input.
- Keeps critical loads running in a grid outage, with backup switchover in under 10ms.
- Built-in air conditioning plus layered fire suppression: aerosol, explosion relief valve and fire water inlet.
SolisStorage EverCore 120kWh battery and 60kW hybrid inverter system
The SolisStorage EverCore 120kWh battery and 60kW hybrid inverter system (EverCore-120kWh-60kW-NV) pairs a 120.6kWh LFP battery cabinet with a Solis S6-EH3P60K-H inverter. It stores solar or off-peak grid energy, cuts peak demand and backs up three-phase loads. Battery management, monitoring and connections for grid, load and a diesel generator are built in.
Key features
- Six 20.1kWh battery packs built from 3.2V / 314Ah LFP cells, rated for 8,000 cell cycles (cell manufacturer data, 25°C, 0.5P, 70% SOH).
- Rated at 60kW / 60kVA on-grid. Backup output can briefly reach 1.5× rated power for 10 seconds or 1.6× for 2 seconds.
- Four MPPTs and 8 PV strings, 1,000V maximum input and a 150–850V MPPT range.
- Off-grid parallel operation of up to 10 units, with a dedicated GEN port for a diesel generator.
- SolisCloud app setup over Bluetooth, plus WiFi, LAN, CAN, RS485, DRM and dry contacts (4G optional).
Where to use
This system suits three-phase commercial and industrial sites. Examples include logistics depots, cold stores, farms, workshops, factories, schools and EV charging hubs.
Typical uses are solar self-consumption, peak shaving, time-of-use tariff shifting, backup for critical loads, and off-grid or weak-grid sites running alongside a generator.
Installation and site requirements
The system is not plug-and-play. The cabinet and inverter ship separately and are assembled on site. Lifting needs a crane or forklift rated for at least 3 tonnes. Energian can arrange design, installation and commissioning through trusted partners.
Install outdoors on a level, solid base at least 200mm high. Keep at least 1,200mm behind the cabinet and about 2,000mm clear in front. Grid connection needs DNO approval, and an external ATS is needed if you want a bypass. EverCore is not a UPS.
Solar panels, mounting, cabling, switchgear and grounding are not included. They can be quoted to suit your site.
SolisStorage EverCore 120kWh / 60kW technical specifications
| Specification | EverCore-120kWh-60kW-NV |
|---|---|
| System | |
| Rated energy capacity | 120.6kWh (manual: 120.576kWh) |
| Usable energy capacity | 119.2kWh (30–35°C, 0.3C, 100% DOD, within one month of manufacture) |
| Nominal charging / discharging power | 60kW / 60kW |
| Max. cycle rate | 0.5P |
| Max. cycle efficiency | 89% (cell test at 25 ±2°C, 0.5P, AC output 380 or 400Vac) |
| Dimensions (W × H × D) | 1,250 × 2,030 × 1,540mm |
| Dimensions without inverter (W × H × D) | 950 × 2,030 × 1,540mm |
| Weight | 1,630kg (cabinet) + 73kg (inverter) |
| Operating temperature range | -25 to +55°C (manual: charging 0 to +55°C, discharging -25 to +55°C) |
| Storage temperature range | 0 to +40°C |
| Transportation temperature | -30 to +55°C; humidity ≤85% (no condensation) |
| Operating humidity range | ≤95% (non-condensing) |
| Max. operation altitude | 4,000m (derating above 2,000m) |
| System temperature control mode | Industrial-grade air-conditioning (cabinet); air cooling (pack); intelligent fan-cooling (inverter) |
| Fire suppression mode | Default: aerosol, explosion relief valve, fire water inlet, audible and visual alarm. Optional: flammable gas detector, explosion relief panel, explosion-proof exhaust fan |
| Fire detection | Smoke detector and temperature detector (standard); aerosol releases at 170 ±5°C cabinet temperature; DN65 fire water inlet connector |
| Ingress protection | IP55 (cabinet) + IP66 (inverter) |
| Anti-corrosion class (battery cabinet) | C4 / C5 (optional) |
| Anti-corrosion class (inverter) | C5 |
| Noise (rated operating condition) | 70dB(A) at 1m |
| Lightning protection | Type II (AC port), Type II (PV & battery) |
| Protection mode | Anti-islanding protection, residual current detection, insulation resistance detection, AC overcurrent protection, AC cable connection protection |
| Auxiliary power supply | 220Vac, approx. 2.3kW (taken from the inverter backup port) |
| Communication protocol (cabinet) | TCP/IP, CAN, RS485 |
| Certification standards (datasheet) | IEC 62619, IEC 61000-6-2/4, IEC 62040, IEC 63056, IEC 62477, UN38.3 |
| Compliance standards (manual) | UN38.3, IEC 62619, IEC 60730-1, IEC 63056, IEC 62477-1, IEC 61000-6-2 / IEC 61000-6-4, UN3480 |
| Battery | |
| Cell type | LFP 3.2V / 314Ah (EVE MB31, 5.6 ±0.2kg) |
| Cell cycle life | 8,000 (cell manufacturer data at 25 ±2°C, 0.5P charge and discharge, SOH = 70%) |
| System battery configuration | 1P120S |
| Rated voltage | 384V |
| Operating voltage range | 348–432V |
| Rated DC current | 157A |
| Number of battery packs | 6 |
| Battery pack model | PACK-1P20S-314-01 |
| Battery pack capacity | 20.1kWh |
| Battery pack rated voltage / range | 64V / 58–72V |
| Battery pack charge and discharge rate | ≤0.5C |
| Battery pack weight | 138kg |
| Battery pack dimensions (W × H × D) | 435 × 230 × 904mm |
| Battery pack ingress protection | IP20 |
| Balancing mode | Passive cell balancing |
| Pack communications port | CAN 2.0 |
| Inverter | |
| Inverter model | S6-EH3P60K-H(21A) |
| Rated output power | 60kW |
| Max. apparent output power (on-grid) | 60kVA |
| Rated grid voltage | 3/N/PE, 220V / 380V; 3/N/PE, 230V / 400V |
| Rated grid frequency | 50Hz / 60Hz |
| AC grid frequency range | 45–55Hz / 55–65Hz |
| Rated output current | 91.2A / 86.6A |
| Max. apparent output power (off-grid) | 1.5 × rated power, 10s; 1.6 × rated power, 2s |
| Back-up switch time | <10ms |
| Power factor | >0.99 (0.8 leading – 0.8 lagging) |
| THDi / THDv (at linear load) | <2% / <3% |
| Max. usable PV input power | 100kW |
| Recommended max. PV array size | 100kW |
| Max. input voltage | 1,000V (reduces above 2,000m: 981V at 3,000m, 925V at 3,500m, 875V at 4,000m) |
| Rated voltage | 600V |
| Start-up voltage | 180V |
| MPPT voltage range | 150–850V |
| Max. input current | 4 × 42A |
| Max. short circuit current | 4 × 60A |
| MPPT number / max. input strings number | 4 / 8 |
| Communication | Standard: WiFi + LAN + Bluetooth, CAN-BMS × 2, CAN-Parallel × 2, RS485-Meter, RS485, DRM, DI × 3, DO × 3. Optional: 4G |
| Max. parallel quantity (off-grid) | 10 |
| AC ports | Grid, Backup (user load), GEN (diesel generator) |
| Thermal management (air conditioner) | |
| Refrigerant | R134a |
| Refrigerating / heating capacity | 3,200W / 1,000W |
| Rated power (refrigerating / heating) | 1,600W / 1,200W at 50Hz; 1,800W / 1,300W at 60Hz |
| Rated voltage / frequency | 220Vac ±15% / 50/60Hz |
| Installation | |
| Foundation | Concrete or level ground, foundation height ≥200mm; load capacity 1.5 × n tonnes (n = number of units); 4 fixing points with M12 bolts |
| Clearances | Back to wall ≥1,200mm; front to wall 2,000mm recommended; back to back ≥500mm; facing units ≥2,500mm; inverter side ≥500mm (follow local fire authority requirements) |
| Grounding | Equipment continuity <0.1Ω; system grounding resistance ≤4Ω |
| Recommended grid cable | L1/L2/L3/N 50mm²; PE 25mm² |
| Recommended generator cable | 16mm² (A/B/C/N/PE) |
| Lifting | Lifting equipment >3t, 4 cables >1m, acceleration ≤0.2g; forklift and crane load capacity ≥3,000kg |
| Supplied accessories | Sun shade, left and right side panels, front panel, bottom panel, 10 × M6×12 stainless steel screws |
Documents available for download
- SolisStorage EverCore datasheet
- SolisStorage EverCore user manual
- SolisStorage EverCore quick installation manual
Shipping
Shipping is available to the UK, Ireland, Africa, the Caribbean and worldwide. If a shipping rate is not shown at checkout, call +44 20 8064 0335 or email info@energian.co.uk for a quote. Delivery, unloading and site access are agreed for each order.
UK expert support
Our UK team can help you size an EverCore system, plan the PV array, generator and grid connection, and arrange installation. Contact us by phone, email or live chat, or visit our office for an in-person consultation.