Fox ESS H3 Smart 3ph 12.0KW Hybrid Inverter

  
By Fox ESS

Delivery available

Fox ESS H3 Smart 3ph 12.0kW HV Hybrid Inverter

  • Solar, high-voltage battery storage and three-phase backup power from one wall-mounted IP65 unit.
  • Takes up to 24,000Wp of PV across 3 MPPT trackers, so you can fit larger or split-orientation roofs.
  • Keeps three-phase loads running in a power cut, with up to 12,000VA EPS output.

Fox H3 Smart 12.0kW 3ph hybrid inverter

The Fox H3 Smart 12.0kW 3ph hybrid inverter (model H3-12.0-Smart) is a three-phase inverter for 100–800V lithium-ion (LFP) batteries. It powers your loads from solar, charges the battery with surplus energy and exports the rest to the grid. It supplies backup power during outages, and FoxCloud V2.0 handles remote monitoring by app or web portal.

Key features

  • 12,000W nominal AC output (13,200VA maximum) and 97.9% maximum efficiency, with 97.2% European efficiency.
  • Battery charges and discharges at up to 50A over a 100–800V range. Fox designs it around high-voltage batteries for maximum round-trip efficiency.
  • Work modes include self-use, feed-in priority, backup, peak shaving and time-scheduled charging. Export limitation by CT, meter, DRM0 or E-stop.
  • Unbalanced output mode supplies each phase to match its own load, up to one third of rated power per phase.
  • Built-in DC switch and Type II PV and AC surge protection. AFCI arc-fault protection is available as an option.

Where to use

The H3 Smart 12.0kW suits larger homes, farms, workshops, schools, retail units and small commercial premises with a three-phase supply. Typical uses include higher solar self-consumption, cheap-rate battery charging, peak shaving and backup for three-phase pumps, heat pumps or machinery.

Up to 10 units can run in parallel for bigger sites. The IP65 rating and -25°C to +60°C operating range (derating from 45°C) allow installation outdoors, in plant rooms or in outbuildings.

Installation and grid connection

This inverter is not plug-and-play. It needs a compatible high-voltage LFP battery, a meter or CT and installation by a qualified installer. For this size, that includes a G99 application to your DNO. Energian can arrange installation through trusted UK partners.

Order installation through our trusted partners and pay zero VAT. Installers can call 020 8064 0335 to join our authorised partner network.

Fox H3 Smart 12.0kW (H3-12.0-Smart) technical specifications

Specification H3-12.0-Smart
PV input
Max. array power 24,000Wp
Max. DC input power 22,500W
Max. DC voltage 1,000V (for a 1,000V system, max. PV operating voltage is 950V)
Nominal DC operating voltage 620V
Max. MPPT input current 20 / 20 / 20A
Max. MPPT short-circuit current 25 / 25 / 25A
Max. MPPT input power 10,000 / 10,000 / 10,000W
Min. operating PV voltage 90V (starting working voltage of the power supply)
MPPT voltage range 120–950V
MPPT voltage range (full load) 210–850V
Start-up input voltage 140V
No. of MPP trackers 3
Strings per MPP tracker 1+1+1
Battery
Battery type Lithium-ion battery (LFP)
Battery voltage 100–800V
Min. operating battery voltage 100V
Min. battery voltage at full AC load 250V
Max. charge / discharge current 50.0A
Communication interface CAN
AC output
Nominal AC power 12,000W
Max. apparent AC power 13,200VA
Rated grid voltage (AC voltage range) 400/230Vac; 380/220Vac, 3L/N/PE
Rated grid frequency 50 / 60Hz, ±5Hz
Rated AC current (per phase) 18.2A
Max. AC current (per phase) 20.0A
Power factor 1 (adjustable from 0.8 leading to 0.8 lagging)
Export control Yes
AC inrush current 15A @ 0.5ms
Max. output fault current 150A @ 0.5ms
Max. output overcurrent protection 50A
THDi <3% at rated power
AC input
Max. AC power 14,400VA
Rated grid voltage (AC voltage range) 400/230Vac; 380/220Vac, 3L/N/PE
Rated grid frequency 50 / 60Hz, ±5Hz
Max. AC current (per phase) 21.8A
AC inrush current 15A @ 0.5ms
EPS output (with battery)
Max. apparent AC power 12,000VA
Peak apparent AC power (60s) 14,400VA
Rated output voltage 400/230Vac; 380/220Vac, 3L/N/PE
Rated frequency 50 / 60Hz
EPS max. current (per phase) 17.4A
Power factor 1 (adjustable from 0.8 leading to 0.8 lagging)
Switch time <10ms (datasheet V1.9); the user manual V1.0.4 states <20ms
THDv <3% at linear load
Parallel operation Yes, max. 10 units
Efficiency
MPPT efficiency 99.90%
Max. efficiency 97.90%
European efficiency 97.20%
Protection
PV reverse polarity protection Yes
Battery reverse protection Yes
Anti-islanding protection Yes
Output short-circuit protection Yes
Leakage current protection Yes
Insulation resistance detection Yes
Overvoltage category III (AC side), II (DC side)
Reverse connection protection Yes
Overcurrent / overtemperature protection Yes
DC / AC surge protection Type II (PV) / Type II (AC)
AFCI protection Optional
DC switch Yes
General data
Dimensions (W × H × D) 600 × 450 × 226mm
Packing dimensions (W × H × D) 665 × 545 × 390mm
Net weight 34kg
Gross weight 40kg
Installation Wall-mounted
Operating temperature range -25°C to +60°C (derating at 45°C)
Storage temperature -40°C to +70°C
Storage / operation relative humidity 0–100%
Altitude <4,000m (derating above 2,000m)
Protective class I
Ingress protection IP65 (for outdoor use)
Standby consumption 20–25W
Standby mode Yes
Cooling Fan cooling
Noise grade <55dB
Inverter topology Non-isolated
Communication interface Ethernet, EMS (RS485), Meter, WiLAN (Wi-Fi + LAN + Bluetooth), 4G (optional), DRM, Ripple Control, USB, BMS (CAN), SG Ready
LCD display Backlit, 16 × 4 characters
Buttons Capacitive touch sensor × 4
Buzzer 1, inside (EPS and earth fault)

Documents available for download

Shipping

Shipping is available to the UK, Ireland, Africa, the Caribbean and worldwide. If a shipping rate is not shown at checkout, call +44 20 8064 0335 or email info@energian.co.uk for a quote.

UK expert support

Our UK team can help you match batteries, plan PV strings, design parallel systems and arrange installation. Contact us by phone, email or live chat, or visit our office for an in-person consultation.