Fox H3 Plus 100.0kW 3ph HV Hybrid Inverter
- Solar, high-voltage battery storage, backup power and diesel generator input in one 100kW commercial unit.
- Keeps critical site loads running in a power cut, with on/off-grid switchover in under 10ms.
- Takes up to 200kW of PV on 8 MPPT trackers and charges batteries at up to 240A through 3 battery ports.
Fox H3 Plus 100.0kW 3ph hybrid inverter
The Fox H3 Plus 100.0kW 3ph hybrid inverter (model H3-100-Plus) is a commercial three-phase storage inverter for 380/400V supplies. It runs site loads from solar, stores surplus energy in high-voltage batteries and exports to the grid. If the grid fails, it switches to backup power and can start a diesel generator automatically. Monitoring runs through FoxCloud V2.0.
Key features
- 100kW rated output (110kVA maximum), a 155kVA peak for 10 seconds and 300A LRA current for motor and compressor starts.
- Supports 100% unbalanced three-phase output, which suits sites with mixed single-phase and three-phase loads.
- The generator input takes up to 207kVA and 300A. Automatic generator control starts and stops the set based on battery SOC, load demand and grid availability.
- 98.5% maximum and 98.1% European efficiency, with AFCI arc-fault protection (IEC63027), string current monitoring and Type II AC/DC surge protection.
- Up to 10 units in parallel, plus a DC-link connection ready for a 20–50kW EV charger.
Where to use
The H3 Plus 100kW suits warehouses, logistics hubs, factories, farms, cold stores, offices, retail parks and public buildings with a three-phase supply. Typical uses include solar self-consumption, peak demand reduction, tariff shifting and backup for refrigeration, IT, lighting and production lines.
With generator input and parallel operation, it also suits weak-grid and remote sites. The IP65 rating and -30°C to +60°C operating range allow indoor or outdoor installation on a wall or bracket.
Installation and grid connection
This is a commercial system, not a plug-and-play product. It needs system design, compatible Fox ESS high-voltage batteries, meters and protection, and installation by qualified electricians. A G99 application to your DNO is also required. Energian can arrange design and installation through trusted UK partners.
Order installation through our trusted partners and pay zero VAT. Installers can call 020 8064 0335 to join our authorised partner network.
Fox H3 Plus 100.0kW (H3-100-Plus) technical specifications
| Specification | H3-100-Plus |
|---|---|
| PV input | |
| Max. array power | 200kW |
| Max. input power | 200kW |
| Withstand voltage / max. DC voltage | 1,000V |
| Nominal DC operating voltage | 750V |
| Input voltage range | 180–950V |
| Max. MPPT input current | 40A |
| Max. MPPT short-circuit current | 50A |
| MPPT voltage range | 180–850V |
| MPPT voltage range (full load) | 370–850V |
| Max. inverter backfeed current to array | 0A |
| Start-up voltage | 180V |
| No. of MPP trackers | 8 |
| Strings per MPP tracker | 2 |
| DC input terminals | 16 pairs of PV connectors |
| Battery | |
| Battery type | LFP (LiFePO₄) |
| Battery voltage range | 180–950V |
| Nominal voltage | 700V |
| Full AC load battery voltage | 490–820V |
| Max. charging / discharging current | 240A (80 + 80 + 80A) |
| Battery ports | 3 |
| Communication | CAN × 3 |
| AC output (grid) | |
| Nominal / rated AC power | 100kW |
| Rated apparent power | 100kVA |
| Max. active power | 110kW |
| Max. AC output power | 110kVA |
| Rated AC output current (per phase) | 151.9A (datasheet); 152A at 380V, 144.4A at 400V (manual) |
| Max. AC output current (per phase) | 167.2A at 380V; 158.8A at 400V |
| Nominal AC voltage | 380/400V, 3W+N+PE or 3W+PE |
| AC voltage range | 0.8–1.2 Un |
| Nominal AC frequency | 50 / 60Hz |
| Frequency range | 50 / 60Hz, ±5Hz |
| Power factor | 0.8 leading to 0.8 lagging |
| THDi | <3% at rated power |
| Max. output fault current | 582A, 68µs |
| AC inrush current | 100A, 1ms |
| Max. output overcurrent protection | 280A rms, 398A peak |
| Export control | Yes |
| DC injection current | 0.5% of rated current |
| AC input (grid) | |
| Max. AC input power | 207kVA |
| Max. bypass / input current | 300A |
| Max. AC power for battery charging | 100kW |
| Max. AC current for battery charging | 152A |
| Nominal AC voltage | 380/400V, 3W+N+PE or 3W+PE |
| Frequency range | 50 / 60Hz, ±5Hz |
| Power factor | 0.8 leading to 0.8 lagging |
| EPS output (load, with battery) | |
| Rated power | 100kW / 100kVA |
| Max. AC output power | 110kVA |
| Peak AC output power (10s) | 155kVA |
| Rated AC output current | 152A |
| Max. AC output current | 167.2A |
| Peak current (off-grid) | 225A, 10s |
| LRA current | 300A |
| Nominal AC voltage | 380/400V, 3W+N+PE or 3W+PE |
| Nominal AC frequency | 50 / 60Hz |
| On/off-grid switching time | <10ms |
| THDv | <3% (linear load) |
| Parallel operation | Yes, max. 10 units |
| Diesel generator input | |
| Max. AC apparent power | 207kVA |
| Rated AC voltage | 220/380V; 230/400V, 3W+N+PE or 3W+PE |
| Max. AC input current | 300A |
| Rated AC frequency | 50 / 60Hz |
| Power factor | 0.8 leading to 0.8 lagging |
| Max. THDi | <3% at rated power |
| Efficiency | |
| MPPT efficiency | 99.9% |
| Max. efficiency | 98.5% |
| European efficiency | 98.1% |
| Protection | |
| DC input switch | Yes |
| Battery reverse polarity protection | Yes |
| PV reverse polarity protection | Yes |
| Anti-islanding protection | Yes (active method: reactive power disturbance) |
| AC overcurrent protection | Yes |
| AC output short-circuit protection | Yes |
| AC / DC surge protection | Class II (Type II / Type II) |
| ISO (insulation resistance) detection | Yes |
| Residual / leakage current detection | Yes |
| Ground fault detection | Yes |
| Reverse connection protection | Yes |
| Overvoltage category | III (AC side), II (DC side) |
| AFCI | Yes – full coverage, integrated AFPE, classification F–I–AFPE–1–16–1, IEC63027 |
| AFCI rated channel current | 320A (max. 20A per input port) |
| Terminal overtemperature protection | Yes |
| String current detection / monitoring | Yes |
| General data | |
| Dimensions (W × H × D) | 730 × 1,060 × 305mm |
| Weight | 120kg |
| Installation | Bracket-mounted or wall-mounted |
| Operating temperature | -30°C to +60°C |
| Storage temperature | -40°C to +70°C |
| Cooling method | Smart air cooling |
| Operating altitude | 4,000m |
| Humidity | 0–100% |
| Noise | <70dB |
| Standby consumption | <60W |
| Idle mode | Supported |
| DC-link EV charger ready | 20–50kW |
| Ingress protection | IP65 |
| Protective class | I |
| Topology | Non-isolated |
| Display | LED, colour LCD, Wi-Fi + app |
| Buttons | Capacitive touch sensor × 4 |
| Communication ports | USB / RS485 / Bluetooth / Wi-Fi + LAN / 4G (optional) / CAN |
| Radio | Wi-Fi 2.4GHz (2,412–2,472MHz, max. 19dBm) or Bluetooth (2,402–2,480MHz, max. 8dBm) |
Documents available for download
Shipping
Shipping is available to the UK, Ireland, Africa, the Caribbean and worldwide. If a shipping rate is not shown at checkout, call +44 20 8064 0335 or email info@energian.co.uk for a quote.
UK expert support